Example Wind Farm — Cable network report

Example Wind Farm

Reticulation project report generated from the EmptyOS cable-network app on 2026-05-26T01:25:43.

  • Cables: 6
  • Buses / nodes: 16
  • Frequency: 50 Hz
  • Ambient: 20.0 °C
  • Soil ρ_T: 1.00 K·m/W
  • Max conductor temp: 90 °C

Cable schedule

ID Label Library Length (m) Install Iz (A) I (A) I/Iz % ΔV % Status
cable-1 CBL-SUB-RMU1-001 nexans_19-33kv_cu_1c_400 283.0 direct_buried 546 683.0 125.0 -0.12 FAIL
cable-2 CBL-SUB-RMU2-001 nexans_19-33kv_cu_1c_400 283.0 direct_buried 546 683.6 125.1 -0.12 FAIL
cable-3 CBL-RMU1-WTG01-001 nexans_19-33kv_cu_1c_95 424.0 direct_buried 546 114.0 20.9 -0.03 OK
cable-4 CBL-RMU1-WTG02-001 nexans_19-33kv_cu_1c_95 283.0 direct_buried 546 227.9 41.7 -0.04 OK
cable-5 CBL-RMU1-STRINGA-001 nexans_19-33kv_cu_1c_240 424.0 direct_buried 546 341.8 62.6 -0.09 OK
cable-6 CBL-RMU2-STRINGB-001 nexans_19-33kv_cu_1c_300 500.0 direct_buried 546 455.5 83.4 -0.14 WARN

Load-flow

  • Total losses: 0.00 kW
  • Worst utilisation: 125.1 % (CBL-SUB-RMU2-001)

Short-circuit

Short-circuit has not been run for this project.

Methodology

  • Ampacity (Iz): IEC 60287-1-1 (native engine) or CIGRE TB 963 V5 FEM where method selected.
  • Load-flow: backward/forward-sweep (Gauss-Seidel).
  • Short-circuit: IEC 60909 symmetric three-phase fault at each bus, Thevenin impedance reduction.
  • Generated by EmptyOS cable-network app for project demo-windfarm-50mw.